About Linetroll 110Eur
Our best-selling product worldwide with hundreds of thousands of units deployed across the globe.
The Linetroll 110Eµr fault passage indicator is a reliable solution for detecting phase-to-phase (PTP) and phase-to-earth (PTE) faults in 6-50kV distribution networks. This cutting-edge device provides independent, clear visual alerts for both permanent and transient faults using bright, highly visible LEDs with strobe-effect.
Seamlessly integrated with a pole-mounted communication unit (Collector), the system ensures all alarms, status updates, and load current data are wirelessly transmitted via an efficient encrypted RF link. Moreover, the Collector enables remote configuration of the indicators through the same 2.4GHz radio connection, streamlining maintenance and enhancing operational efficiency.
The Linetroll 110Eµr fault passage indicator—designed to optimize fault detection and communication for modern distribution networks.
Two types of GSM enabled collectors are available for this version of the Linetroll 110Eµr: a standalone pole-mounted unit with long-lasting built-in batteries, Linetroll R130CQ and a type that maintains constant communication with SCADA via the IEC60870-5-104 protocol, Comtroll R200C. The latter requires charging, either through a solar panel or a fixed voltage source (mains).
Technical specifications
- System Voltage
- MV– voltage network (6-50kV)
- Grounding system
- Isolated, resistor and solidly grounded.
- Sensitivity PtG di/dt:
- 6, 12, 25, 60, 90, 120, 160 [A]
- PtP threshold:
- 100, 200,500 or 600 [A]
- Inrush blocking
- 10 sec
- Response time
- 20ms, 50ms, 100ms, 200 [ms]
- Reset:
- Not specified
- Automatic
- Renergized line (Voltage or current programmable)
- Timer
- 2, 4, 8, or 16 hours
- Manual
- Handheld unit (FDP-15) or KBN-4 from ground
- Remote
- From SCADA or smartphone App
- Indication LOCAL
- Green LED for transient fault
- High visibility red strobe-flash LED for permanent fault (40 lumens > 500m(day) / 2km(night) 360° visibility).
- Low battery indication amber LED when <20% of total capacity remaining
- Indication REMOTE
- Sends alarm to the communication “collector” by radio with the following:
- Transient Fault Alarm (temporary faults)
- Permanent Fault Alarm
- Loss of voltage or loss of load current alarm
- Load current value in Amps (3—350A)
- Low battery warning (when <20% remaining capacity
- Communication status between collector and indicators
- Radio Communication
- 2,4GHz ISM band
- 1mW (0dBm)
- 1Mbit/s
- 25m LOS (margin= 20dB/Rec.sens:-90dBm)
- Power supply
- 1 pcs Lithium D-size primary battery 19Ah
- Mounting
- Live-line mounting with Grip-All-Clamp hot-stick of KNB-4 mounting tool
- Conductor size
- 5– 36 mm (bare and covered conductors)
- Temperature range
- -40 to +85 deg
- Housing
- Polycarbonate, UV stablized
- Dimension
- 202x54 mm (Box size: 235x65x85 [mm])
- Weight
- 345g including battery
- Degree of protection
- IP68, IK09 (EN60529 & EN62262)