Skip to content
Nortroll – Sicame Group
Linetroll

Linetroll 110Eμ

Linetroll 110Eμ is a line mounted indicator for detection of PtG and PtP faults in overhead line networks.

  • Single distribution systems
  • Distribution systems with earth-wire
  • Multiple distribution systems
Linetroll 110Eμ

About Linetroll 110Eμ

The indicator is powered by replaceable long-life lithium batteries which have a life expectancy of 10-15 years. It provides a 360 degree visibility for indication both for transient faults and permanent faults.

Technical specifications

Application
  • Short circuit and Earth fault indication for overhead lines.
  • System Voltage: MV voltage network (6-69kV)
  • Grounding system: Isolated, resistor and solidly grounded
  • Frequency: 50Hz / 60 Hz
Fault-detection
  • Sensitivity Di/Dt (50Hz): 6, 12, 25, 60 or 120A*
  • Sensitivity threshold (50Hz): 250, 500, 750 or 1000A*
  • Duration: > 60ms (Any value upon request)
  • Inrush-blocking: 5 sec
  • CB-tripping: Within 5 sec
Reset
  • Automatic: Re-energized line (Voltage or current, programmable)
  • Timer: 2, 6, 12, or 24 hours*
  • Manual: By magnet/Mounting-reset tool
Note
  • * All threshold, timers etc. are selectable and programmable by microswitches.
Indication
  • 3 high intensity LED’s
  • Intensity: < 40 lumens for Permanent faults
  • Permanent faults: Ultra Bright Red Strobe Flash
  • Transient faults: 1 green LED (f = 0,2Hz)
  • Low battery: 1 LED (f = 0,1Hz) IF Tot. time >5year OR <20% of tot capacity (16,5Ah) left
Visibility day/night/dir.
  • <500m/2km / 360°
Power supply
  • 1 Lithium Cell, D size tot capacity: 16,5 Ah
  • Battery change: Every 1500 flash hours, normally every 10 years, 15 year shelf life.
Mounting
  • Hot-stick: Live-line mounting with Grip-All Clamp hot-stick or KBN-4 mounting tool.
  • Conductor size: 5-36 mm
Temperature range
  • -40° to +70°C
Housing
  • Material: Polycarbonate, UV stabilized
  • Dimension: 202 x 54mm (with box 235 x 65 x 85)
  • Weight: 345g incl. battery
Protection
  • Ingress: EN 60529 IP 64
  • Mechanical Impact: EN 62262 IK 09 (10J)

Documents and links

Request documentation

Are you ready to work smarter towards reliable and green energy supply?